BF-2049-26
System details
- Type
- Service Penetration
- Element
- Floor
- Substrate
- AAC Floor
- Minimum Substrate Thickness
- 150 mm
- FRL / FRR
- -/240/240
- Trade
- Electrical
- Service
- TPS
- Fire Rating
- 240
Fire-stopping products
Application dimensions
- Aperture
- 30 mm
- Sealant Depth
- 25 mm
- Sealant Fillet
- 0 mm
Specimen size & details
Up to 6 x 2.5 mm², 2C+E TPS Power Cables. Sealant to depth of 25 mm in annular gap to backing rod finished flush both sides.