BF-2061-14
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- BOSS Batt Dbl – Pattress
- Minimum Substrate Thickness
- 75 mm
- FRL / FRR
- -/120/120
- Trade
- Electrical
- Service
- Multicore / Mains / Orange Circular
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Aperture
- 300 x 100 mm
- Sealant Depth
- 75 mm
- Sealant Fillet
- 0 mm
Specimen size & details
•10 × (A1) small sheathed (PVC/PVC) 5 x 1.5 mm2,
•10 × (A2) small sheathed (EPR/PO) 5 × 1.5 mm2,
•10 × (A3) small sheathed (XLPE/EVA) 5 × 1.5 mm2,
•2 × (B) small sheathed (PVC/PVC) 1 × 95 mm2,
•Up to 63 mm HDPE pipe.
Sealant to depth of wall in annular gap applied in the voids around the cables and pipe in a maximum aperture of 300 mm wide x 100 mm high.