BF-2104-26

System details

Type
Service Penetration
Element
Floor
Substrate
AAC Floor
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2104-26 system drawing

Application dimensions

Min Diameter
125 mm
Max Diameter
125 x 7.4 mm
Service Diameter Range
125 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

125 mm x 7.4 mm wall thickness PVC pipe. Sealant 25 mm deep in annular gapfinished flush both sides. The sealant was supported by 10 mm diam. Polyethylene back rods.

Resources