BF-2114-1
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Single Layer
- Minimum Substrate Thickness
- 118 mm
- FRL / FRR
- -/90/90
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 90
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 43 mm
- Service Diameter Range
- Up to 43 mm
- Annular Gap
- 21.5 mm
- Sealant Depth
- 13 mm
- Sealant Fillet
- 0 mm
Specimen size & details
1-direction sealing installation . System is approved for installation in both directions.
Up to 43 mm uPVC pipe. Sealant depth of plasterboard in annular gap finished flush.