BF-2114-12

System details

Type
Service Penetration
Element
Wall
Substrate
Shaftliner 
Minimum Substrate Thickness
118 mm
FRL / FRR
-/90/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
90

Fire-stopping products

BF-2114-12 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
43 mm
Service Diameter Range
Up to 43 mm
Annular Gap
21.5 mm
Sealant Depth
13 mm
Sealant Fillet
0 mm

Specimen size & details

1-direction sealing installation . System is approved for installation in both directions.
Up to 43 mm uPVC pipe. Sealant depth of plasterboard in annular gap finished flush.

Resources