BF-2158-14

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Pattress
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
CPVC
Fire Rating
120

Fire-stopping products

BF-2158-14 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
32 mm
Service Diameter Range
Up to 32 mm
Aperture
83 mm
Annular Gap
25.5 mm
Sealant Depth
20 mm
Sealant Fillet
15 mm

Specimen size & details

cPVC 32 mm (OD42 mm) pipe. Sealant 20 mm depth in annular and a 15 mm x 15 mm fillet both sides.