BF-2188-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2188-25 system drawing

Application dimensions

Min Diameter
125 mm
Max Diameter
125 x 4.8 mm
Service Diameter Range
125 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

125 mm x 4.8 mm wall thickness PVC pipe. Sealant to depth of 25 mm in annular gap to backing rod finished flush both sides.

Resources