BF-2285-9

System details

Type
Service Penetration
Element
Wall
Substrate
AFS
Minimum Substrate Thickness
96 mm
FRL / FRR
-/90/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Insulated Copper Pipe
Fire Rating
90

Fire-stopping products

BF-2285-9 system drawing

Application dimensions

Min Diameter
80 mm
Max Diameter
159 mm
Service Diameter Range
80-159 mm
Aperture
Up to 1100 x 1100 mm
Annular Gap
5 mm
Sealant Depth
5 mm
Sealant Fillet
0 mm

Specimen size & details

80 mm - 159mm Copper pipe with continuous 30 - 50 mm Thermobreak tube lagging. Sealant 5 mm deep in 5 mm annular gap both sides. BOSS UniWrap™ installed on both sides. P40-MAK Wrap™ 600 mm to both sides. Aperture up to 1100 mm x 1100 mm with 1 layer of BOSS Batt™ pattress fitted over the aperture on both sides with 100 mm overlap of the aperture on all sides.