BF-2302-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Insulated Copper Pipe
Fire Rating
120

Fire-stopping products

BF-2302-25 system drawing

Application dimensions

Min Diameter
32 mm
Max Diameter
159 mm
Service Diameter Range
32-159 mm
Aperture
Min 100 mm clearance around pipe mm
Annular Gap
5 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

32 mm - 159 mm Copper pipe with continuous 30 - 50 mm Thermobreak tube lagging. Sealant 25 mm deep in 5 mm annular gap both sides. Up to 12 layers of BOSS UniWrap™ installed to the underside, depending on pipe size. P40-MAK Wrap™ 300 mm to the top side. Aperture to have minimum 100 mm clearance around the pipe filled with 2 layers of BOSS Batt™ friction fitted flush with the top side.