BF-2309-6

System details

Type
Service Penetration
Element
Wall
Substrate
Speedpanel / Korok
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Electrical
Service
Appendix D2 Config
Fire Rating
120

Fire-stopping products

BF-2309-6 system drawing

Application dimensions

Aperture
Up to 1100 x 1100 mm
Sealant Depth
0 mm
Sealant Fillet
20 mm

Specimen size & details

Appendix D2 Group B cable configuration, consisting of 60 x 50 pair telecommunication cables, installed onto a tray up to 500 mm wide. The tray penetrated 2 layers of BOSS Batt™ protecting an aperture up to 1100 mm x 1100 mm and was sealed with a 20 mm x 20 mm fillet of BOSS FireMastic-300™ on both sides. The system was then wrapped with BOSS P40-MAK Wrap for 300 mm on both sides.