BF-2317-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/30
Trade
Plumbing / Hydraulic / Active Fire
Service
Steel Pipe
Fire Rating
120

Fire-stopping products

BF-2317-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
159 mm
Service Diameter Range
Up to 159 mm
Aperture
Up to 1100 x 1100 mm
Sealant Depth
Fill Gaps mm
Sealant Fillet
0 mm

Specimen size & details

Up to 159 mm steel pipe penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1100 mm x 1100 mm, with P40-MAK Wrap™ insulation 300 mm to both sides. FireMastic-300™ is applied to any gaps around the pipe.