BF-2326-21

System details

Type
Service Penetration
Element
Wall
Substrate
Permanent Polymer Formwork
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/-
Trade
Plumbing / Hydraulic / Active Fire
Service
Insulated Steel Pipe
Fire Rating
120

Fire-stopping products

BF-2326-21 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
80 mm
Service Diameter Range
Up to 80 mm
Aperture
Up to 1100 x 1100 mm
Sealant Depth
Fill Gaps mm
Sealant Fillet
0 mm

Specimen size & details

Up to 80 mm steel pipe with continuous 50 mm Thermobreak tube lagging, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1100 mm x 1100 mm. FireMastic-300™ is applied to any gaps around the pipe and a 150 mm BOSS MaxiCollar™ is installed to both sides.

Resources