BF-2333-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Steel Pipe
Fire Rating
120

Fire-stopping products

BF-2333-2 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
42 mm
Service Diameter Range
Up to 42 mm
Aperture
Up to 1100 x 1100 mm
Sealant Depth
Fill Gaps mm
Sealant Fillet
0 mm

Specimen size & details

Up to 42 mm steel pipe penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1100 mm x 1100 mm, with P40-MAK Wrap™ insulation 300 mm to both sides. FireMastic-300™ is applied to any gaps around the pipe.