BF-2371-8

System details

Type
Service Penetration
Element
Wall
Substrate
Pronto Panel 
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/-
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2371-8 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
100 mm
Service Diameter Range
Up to 100 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
10.5 mm
Sealant Depth
5 mm
Sealant Fillet
0 mm

Specimen size & details

Up to 100 mm uPVC pipe with 3.8 mm wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant installed around service 5 mm deep in 10.5 mm annular gap finished flush both sides. The system includes a 100 mm BOSS MaxiCollar™ installed to both sides.