BF-2376-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Electrical
Service
Multicore / Mains / Orange Circular
Fire Rating
120

Fire-stopping products

BF-2376-2 system drawing

Application dimensions

Aperture
Up to 1100 x 1100 mm
Annular Gap
Up to 20 mm
Sealant Depth
25 mm
Sealant Fillet
50 mm

Specimen size & details

Cable bundle
-Up to 2.5mm² 2C+E Power Cable
-Up to 3 x 6mm² 3C+E Power Cables
-Up to 8 x 16mm² 3C+E Power Cables
FireMastic-300™ Sealant installed 25mm deep in annular gap up to 20mm wide, finished with a 50 mm x 50 mm fillet both sides. 600mm of Thermal Defence Wrap each side of the wall.