BF-2437-4
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Concrete
- Minimum Substrate Thickness
- 116 mm
- FRL / FRR
- -/120/120
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Copper Pipe
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 54 mm
- Max Diameter
- 159 mm
- Service Diameter Range
- 54-159 mm
- Aperture
- Up to 1100 x 1100 mm
- Annular Gap
- Up to 20 mm
- Sealant Depth
- 25 mm
- Sealant Fillet
- 20 mm
Specimen size & details
54mm - 159mm Copper pipe with maximum wall thickness of 1.0mm. FireSilicone-EMA™ Sealant installed 25mm deep in annular gap up to 20mm wide, finished with a 20 mm x 20 mm fillet both sides. 600mm of Thermal Defence Wrap each side of the wall.