BF-2444-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Iron Pipe
Fire Rating
120

Fire-stopping products

BF-2444-25 system drawing

Application dimensions

Min Diameter
32 mm
Max Diameter
159 mm
Service Diameter Range
32-159 mm
Aperture
Up to 1100 x 1100 mm
Annular Gap
Up to 20 mm
Sealant Depth
25 mm
Sealant Fillet
20 mm

Specimen size & details

32mm - 159mm Iron pipe with maximum wall thickness of 4.5mm. FireMastic-300™ Sealant installed 25mm deep in annular gap up to 20mm wide, finished with a 20 mm x 20 mm fillet on the top side. Thermal Defence Wrap on the top side of the floor with a 600mm 1st layer and 300mm 2nd layer.

Resources