BF-2452-18

System details

Type
Service Penetration
Element
Wall
Substrate
Pronto Panel (w/Buildup) 
Minimum Substrate Thickness
96 mm
FRL / FRR
-/90/90
Trade
Electrical
Service
Multicore / Mains / Orange Circular
Fire Rating
90

Fire-stopping products

BF-2452-18 system drawing

Application dimensions

Annular Gap
Up to 20 mm
Sealant Depth
16 mm
Sealant Fillet
50 mm

Specimen size & details

Cable bundle
-Up to 2.5mm² 2C+E Power Cable
-Up to 3 x 6mm² 3C+E Power Cables
-Up to 8 x 16mm² 3C+E Power Cables
FireMastic-300™ Sealant installed 16mm deep in annular gap up to 20mm wide, finished with a 50 mm x 50 mm fillet both sides. 600mm of Thermal Defence Wrap each side of the wall.