BF-2469-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Electrical
Service
Multicore / Mains / Orange Circular
Fire Rating
120

Fire-stopping products

BF-2469-25 system drawing

Application dimensions

Annular Gap
Up to 20 mm
Sealant Depth
25 mm
Sealant Fillet
50 mm

Specimen size & details

Power Cables:
A1 – PVC/PVC 5mm x 1.5mm² - Approx. Dia 14mm
A1 – EPR/PO 5mm x 1.5mm² - Approx. Dia 11.2-14.4mm
A1 – XLPE/EVA 5mm x 1.5mm² - Approx. Dia 13mm
B – PVC/PVC 1mm x 95mm² - Approx. Dia 18-21mm
D1 – PVC/PVC 4mm x 185mm² - Approx. Dia 52mm
D2 – EPR/PO 4mm x 185mm² - Approx. Dia 64-80mm
D3 – XLPE/EVA 4mm x 185mm² - Approx. Dia 58mm
FireSilicone-EMA™ Sealant installed 25mm deep in annular gap up to 20mm wide, finished with a 50 mm x 50 mm fillet on the top side. Thermal Defence Wrap on the top side of the floor with a 600mm 1st layer and 300mm 2nd layer.