BF-2471-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Electrical
Service
Telecomm
Fire Rating
120

Fire-stopping products

BF-2471-25 system drawing

Application dimensions

Annular Gap
Up to 20 mm
Sealant Depth
25 mm
Sealant Fillet
50 mm

Specimen size & details

Telecommunications Cables:
G1 – PVC/- 1mm x 95mm² - Approx. Dia 14.1-17.1mm
G2 – PVC/- 1mm x 185mm² - Approx. Dia 19.3-23.3mm
FireSilicone-EMA™ Sealant installed 25mm deep in annular gap up to 20mm wide, finished with a 50 mm x 50 mm fillet on the top side. Thermal Defence Wrap on the top side of the floor with a 600mm 1st layer and 300mm 2nd layer.

Resources