BF-2473-1

System details

Type
Service Penetration
Element
Wall
Substrate
Single Layer
Minimum Substrate Thickness
96 mm
FRL / FRR
-/90/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Steel Pipe
Fire Rating
90

Fire-stopping products

BF-2473-1 system drawing

Application dimensions

Min Diameter
113 mm
Max Diameter
159 mm
Service Diameter Range
113-159 mm
Annular Gap
Up to 20 mm
Sealant Depth
16 mm
Sealant Fillet
20 mm

Specimen size & details

113mm - 159mm Steel pipe with maximum wall thickness of 4.5mm. FireMastic-300™ Sealant installed 16mm deep in annular gap up to 20mm wide, finished with a 20 mm x 20 mm fillet both sides. 600mm of Thermal Defence Wrap each side of the wall.