BF-2534-4
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Concrete
- Minimum Substrate Thickness
- 96 mm
- FRL / FRR
- -/90/90
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Iron Pipe
- Fire Rating
- 90
Fire-stopping products
Application dimensions
- Min Diameter
- 32 mm
- Max Diameter
- 80 mm
- Service Diameter Range
- 32 -80 mm
- Annular Gap
- 5 mm
- Sealant Depth
- 5 mm
- Sealant Fillet
- 0 mm
Specimen size & details