BF-2536-4
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Concrete
- Minimum Substrate Thickness
- 116 mm
- FRL / FRR
- -/120/120
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Copper Pipe
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 32 mm
- Max Diameter
- 80 mm
- Service Diameter Range
- 32 -80 mm
- Annular Gap
- 5 mm
- Sealant Depth
- 5 mm
- Sealant Fillet
- 0 mm
Specimen size & details
32 mm - 80 mm Copper pipe. Sealant 5 mm deep in 5 mm annular gap both sides. P40-MAK Wrap™ 300 mm to both sides.