BF-2536-5

System details

Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Copper Pipe
Fire Rating
120

Fire-stopping products

BF-2536-5 system drawing

Application dimensions

Min Diameter
32 mm
Max Diameter
80 mm
Service Diameter Range
32 -80 mm
Annular Gap
5 mm
Sealant Depth
5 mm
Sealant Fillet
0 mm

Specimen size & details

32 mm - 80 mm Copper pipe. Sealant 5 mm deep in 5 mm annular gap both sides. P40-MAK Wrap™ 300 mm to both sides.