BF-2566-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Steel Pipe
Fire Rating
120

Fire-stopping products

BF-2566-25 system drawing

Application dimensions

Min Diameter
32 mm
Max Diameter
159 mm
Service Diameter Range
32-159 mm
Annular Gap
5 mm
Sealant Depth
25 mm
Sealant Fillet
10 mm

Specimen size & details

32 mm - 159 mm Steel pipe. Sealant 25 mm deep in 5 mm annular gap with 10 mm fillet on the top side. P40-MAK Wrap™ 600 mm to the top side.