BF-2602-1
System details
- Type
- Linear Joint
- Element
- Wall
- Substrate
- Single Layer
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- Up to 300 minutes
- Trade
- Construction (Linear Gaps / Blank Seals)
- Fire Rating
- 300
Fire-stopping products
Application dimensions
- Annular Gap
- No greater than 5 mm
- Sealant Depth
- Fill gaps mm
Specimen size & details
Intumescent damper, face fixed to the wall system - Sealant applied to the section of damper in contact with the wall and to any steel brackets attached to the wall. The damper must overlap the wall by at least 50 mm and any gaps must not exceed 5 mm. The FRL is relative the to the stated perfromance of the system.