BF-2619-4

System details

Type
Linear Joint
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
150 mm
FRL / FRR
-/180/180
Trade
Construction (Linear Gaps / Blank Seals)
Fire Rating
180

Fire-stopping products

BF-2619-4 system drawing

Application dimensions

Max Width
12 mm
Max Length
12 mm
Aperture
12 mm
Sealant Depth
6 mm

Specimen size & details

Linear gap seal up to 12 mm wide, with 6 mm deep sealant applied flush with both sides of the wall, backed by a 13 mm PEF backing rod. System installed both sides of a 150 mm thick wall system.