BF-2621-4

System details

Type
Linear Joint
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
150 mm
FRL / FRR
-/180/180
Trade
Construction (Linear Gaps / Blank Seals)
Fire Rating
180

Fire-stopping products

BF-2621-4 system drawing

Application dimensions

Max Width
50 mm
Max Length
50 mm
Aperture
50 mm
Sealant Depth
25 mm

Specimen size & details

Linear gap seal up to 50 mm wide, with 25 mm deep sealant applied flush with both sides of the wall, backed by three 13 mm PEF backing rods. System installed both sides of a 150 mm thick wall system.