BF-2640-18

System details

Type
Service Penetration
Element
Wall
Substrate
Pronto Panel (w/Buildup) 
Minimum Substrate Thickness
90 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
60

Fire-stopping products

BF-2640-18 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
80 mm
Service Diameter Range
Up to 80 mm
Annular Gap
7.5 mm
Sealant Depth
5 mm

Specimen size & details

Up to 80 mm uPVC DWV pipe with 2.9 mm maximum wall thickness. Sealant 5 mm deep in 7.5 mm annular gap both sides. 80 mm BOSS MaxiCollar™ installed on both sides.

Resources