BF-2647-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
90 mm
FRL / FRR
-/45/45
Trade
Plumbing / Hydraulic / Active Fire
Service
HDPE

Fire-stopping products

BF-2647-2 system drawing

Application dimensions

Min Diameter
125 mm
Max Diameter
160 mm
Service Diameter Range
125 - 160 mm
Annular Gap
4 mm
Sealant Depth
5 mm

Specimen size & details

125 mm - 160 mm HDPE pipe with 7.5 mm maximum wall thickness. Sealant 5 mm deep in 4.0 mm annular gap both sides. BOSS MaxiCollar™ relative to pipe size, installed on both sides.