BF-2651-12

System details

Type
Service Penetration
Element
Wall
Substrate
Shaftliner 
Minimum Substrate Thickness
90 mm
FRL / FRR
-/60/45
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
60

Fire-stopping products

BF-2651-12 system drawing

Application dimensions

Min Diameter
32 mm
Max Diameter
125 mm
Service Diameter Range
32 - 125 mm
Annular Gap
10 mm
Sealant Depth
10 mm

Specimen size & details

32 mm - 125 mm PPR pipe with 2.7 mm maximum wall thickness. Sealant 10.0 mm deep in 10.0 mm annular gap both sides. 110 mm BOSS MaxiCollar™ installed on both sides.