BF-2653-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
100 mm
FRL / FRR
-/60/45
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
60

Fire-stopping products

BF-2653-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
32 mm
Service Diameter Range
Up to 32 mm
Annular Gap
10 mm
Sealant Depth
5 mm

Specimen size & details

Up to 32 mm PPR pipe with 2.9 mm maximum wall thickness. Sealant 5.0 mm deep in 10.0 mm annular gap both sides. 32 mm BOSS MaxiCollar™ installed on both sides.