BF-2658-16

System details

Type
Service Penetration
Element
Wall
Substrate
Speedpanel / Korok (w/Buildup)
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
120

Fire-stopping products

BF-2658-16 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
160 mm
Service Diameter Range
Up to 160 mm
Annular Gap
10 mm
Sealant Depth
12.5 mm

Specimen size & details

Up to 160 mm PPR pipe with 4.0 mm - 14.6 mm maximum wall thickness. Sealant 12.5 mm deep in 10.0 mm annular gap both sides. 160 mm BOSS MaxiCollar™ installed on both sides.