BF-2667-5
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Masonry
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/60/45
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- HDPE
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Min Diameter
- 40 mm
- Max Diameter
- 120 mm
- Service Diameter Range
- 40 - 120 mm
- Annular Gap
- 10 mm
- Sealant Depth
- 5 mm
Specimen size & details