BF-2668-1
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Single Layer
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/45/45
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- HDPE
Fire-stopping products
Application dimensions
- Min Diameter
- 120 mm
- Max Diameter
- 150 mm
- Service Diameter Range
- 120 - 150 mm
- Annular Gap
- 10 mm
- Sealant Depth
- 5 mm
Specimen size & details
120 mm - 150 mm HDPE pipe with 11.4 mm - 14.5 mm maximum wall thickness. Sealant 5.0 mm deep in 10.0 mm annular gap both sides. BOSS MaxiCollar™ relative to pipe size, installed on both sides.