System details

Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/45
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
60

Fire-stopping products

BF-2686-5 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
150 mm
Service Diameter Range
Up to 150 mm
Annular Gap
9 mm
Sealant Depth
5 mm

Specimen size & details

Up to 150 mm uPVC pipe with 5.2 mm maximum wall thickness. Sealant 5.0 mm deep in 9.0 mm annular gap both sides. 150 mm BOSS MaxiCollar™ installed on both sides.