BF-2742-24

System details

Type
Service Penetration
Element
Wall
Substrate
Cross Laminated Timber (CLT) 
Minimum Substrate Thickness
110 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
60

Fire-stopping products

BF-2742-24 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
40 mm
Service Diameter Range
Up to 40 mm
Annular Gap
12.5 mm
Sealant Depth
5 mm

Specimen size & details

Up to 40 mm uPVC DWV pipe with 2.0 mm maximum wall thickness. Sealant 5.0 mm deep in 12.5 mm annular gap both sides. 40 mm BOSS MaxiCollar™ installed on both sides.

Resources