BF-2766-12

System details

Type
Service Penetration
Element
Wall
Substrate
Shaftliner 
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
CPVC
Fire Rating
120

Fire-stopping products

BF-2766-12 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
33 mm
Service Diameter Range
Up to 33 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
0.8 mm

Specimen size & details

Up to 33.4 mm cPVC pipe with 2.6 mm wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. The system includes a 40 mm BOSS MaxiCollar™ installed to both sides.