BF-2786-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
120 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2786-25 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
150 mm
Service Diameter Range
Up to 150 mm
Annular Gap
11 mm
Sealant Depth
5 mm

Specimen size & details

Up to 125 mm uPVC pipe with 5.0 mm maximum wall thickness. Sealant 5.0 mm deep in 11.0 mm annular gap both sides. 150 mm BOSS MaxiCollar™ installed on the underside.