BF-2796-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/240/240
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
240

Fire-stopping products

BF-2796-25 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
125 mm
Service Diameter Range
Up to 125 mm
Annular Gap
10 mm
Sealant Depth
5 mm

Specimen size & details

Up to 125 mm PP/PPR pipe with 3.1 mm maximum wall thickness. Sealant 5.0 mm deep in 10.0 mm annular gap on the top side. 125 mm BOSS MaxiCollar™ installed on the underside.