BF-2821-26

System details

Type
Service Penetration
Element
Floor
Substrate
AAC Floor
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/-
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
120

Fire-stopping products

BF-2821-26 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
160 mm
Service Diameter Range
Up to 160 mm
Annular Gap
10 mm
Sealant Depth
10 mm

Specimen size & details

Up to 160 mm PP/PPR pipe with 4.0 mm maximum wall thickness, installed with 2 90° fittings on the underside to form a U-bend that penetrates the separating element twice. Sealant 10.0 mm deep in 10.0 mm annular gap on both sides for each penetration point. 160 mm BOSS MaxiCollar™ installed on both sides of each penetration point.

Resources