BF-2834-27
System details
- Type
- Service Penetration
- Element
- Ceiling
- Substrate
- Fire Rated Plasterboard
- Minimum Substrate Thickness
- 225 mm
- FRL / FRR
- -/60/60
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 65 mm
- Service Diameter Range
- Up to 65 mm
- Annular Gap
- 6 mm
- Sealant Depth
- 5 mm
Specimen size & details
Up to 65 mm uPVC DWV pipe with 2.7 mm maximum wall thickness. Sealant 5.0 mm deep in 6.0 mm annular gap both sides, finished flush. 80 mm BOSS MaxiCollar™ installed on the underside.