BF-2866-2
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Double Layer
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/120/120
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 218 x 74 mm
- Max Diameter
- 218 x 74 mm
- Service Diameter Range
- 218 x 74 mm
- Aperture
- 218 x 74 mm
- Sealant Depth
- Surface mm
Specimen size & details
204 mm x 60 mm uPVC duct with 2.5 mm maximum wall thickness. 3 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap flush with the face of the separating element on both sides. Sealant applied to the ends of the BOSS UniWrap™ or BOSS PWP Pipe Wrap on both sides.