BF-2876-17

System details

Type
Service Penetration
Element
Wall
Substrate
AAC / Hebel (w/Buildup)
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
60

Fire-stopping products

BF-2876-17 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Annular Gap
5 mm

Specimen size & details

Up to 25 mm PEX pipe with 6.2 mm maximum wall thickness. 2 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap encased in a metal sleeve, flush with the face of the separating element on both sides.