BF-2883-5

System details

Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2883-5 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
110 mm
Service Diameter Range
Up to 110 mm
Aperture
Up to 600 x 600 mm
Annular Gap
42 mm
Sealant Fillet
5 mm

Specimen size & details

Up to 110 mm uPVC pipe with 4.2 mm wall thickness, insulated with 32 mm thick phenolic foam. The system penetrated 2 layers of BOSS Batt™, with each layer patressed on either side protecting an aperture up to 600 mm x 600 mm, that overlapped the aperture by 100 mm on all sides. 5 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap flush with the face of the separating element on both sides installed in the 42.0 mm annular gap. 5 mm x 5 mm fillet of sealant applied both sides.

Resources