BF-2951-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2951-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
125 mm
Service Diameter Range
Up to 125 mm
Annular Gap
10 mm
Sealant Depth
10 mm

Specimen size & details

Up to 125 mm uPVC pipe with 7.4 mm wall thickness. Sealant installed around service 10 mm deep in 10 mm annular gap finished flush both sides. The system includes a 125 mm BOSS MaxiCollar™ installed to both sides. Installed in min 100 mm thick walls.