BF-2980-8

System details

Type
Service Penetration
Element
Wall
Substrate
Pronto Panel 
Minimum Substrate Thickness
90 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
60

Fire-stopping products

BF-2980-8 system drawing

Application dimensions

Min Diameter
32 mm
Max Diameter
125 mm
Service Diameter Range
32 - 125 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
10 mm
Sealant Depth
10 mm

Specimen size & details

32 mm - 125 mm PPR pipe with 2.7 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant 10.0 mm deep in 10.0 mm annular gap both sides. 110 mm BOSS MaxiCollar™ installed on both sides.

Resources