BF-2992-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2992-2 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
125 mm
Service Diameter Range
Up to 125 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
10 mm
Sealant Depth
12.5 mm

Specimen size & details

Up to 125 mm uPVC pipe with 6.0 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant 12.5 mm deep in 10.0 mm annular gap both sides. 125 mm BOSS MaxiCollar™ installed on both sides.

Resources