BF-3037-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
116 mm
FRL / FRR
-/30/30
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR

Fire-stopping products

BF-3037-2 system drawing

Application dimensions

Min Diameter
110 mm
Max Diameter
125 mm
Service Diameter Range
110 - 125 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
2 mm
Sealant Depth
5 mm

Specimen size & details

110 mm - 125 mm PPR pipe with 11.4 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant 5.0 mm deep in 2.0 mm annular gap both sides. 125 mm BOSS MaxiCollar™ installed on both sides.