BF-3038-12

System details

Type
Service Penetration
Element
Wall
Substrate
Shaftliner 
Minimum Substrate Thickness
116 mm
FRL / FRR
-/90/90
Trade
Plumbing / Hydraulic / Active Fire
Service
PPR
Fire Rating
90

Fire-stopping products

BF-3038-12 system drawing

Application dimensions

Min Diameter
125 mm
Max Diameter
160 mm
Service Diameter Range
125 - 160 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
10 mm
Sealant Depth
10 mm

Specimen size & details

125 mm - 160 mm PPR pipe with 11.4 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm. Sealant 10.0 mm deep in 10.0 mm annular gap both sides. BOSS MaxiCollar™ relative to pipe size, installed on both sides.

Resources